SCHEDULE I(ss. 10, 14, 15 and 16)
Minimum Distances Authorized for Loading or Unloading Tracks and Racks from Main Tracks, Property Lines and Buildings
Classification | Minimum Distance to Centre Line of Loading or Unloading Track from | Minimum Distance (Feet) to Centre Line of Loading, Unloading Rack or Terminal from — | |||
---|---|---|---|---|---|
Flammable Liquids | Main Track (Gauge side of nearest rail) | Property line of an adjacent Property that has been or may be built upon | Grain Elevators, Ware-houses containing Combustible Materials or Dangerous Commodities; Engine Houses, Railway Shops and Other Similar off site Buildings | Stations, Office Buildings and other similar Places of Public Assembly and nearest Residence | |
Loading | Unloading | ||||
Class I | 50 | 15Footnote for TABLE I Minimum Distances Authorized for Loading or Unloading Tracks and Racks from Main Tracks, Property Lines and Buildings* | 25 | 75 | 150 |
Class II | 30 | 15Footnote for TABLE I Minimum Distances Authorized for Loading or Unloading Tracks and Racks from Main Tracks, Property Lines and Buildings* | 15 | 40 | 75 |
Class III | 50 | 25 | 25 | 75 | 150 |
Return to footnote *Not less than 25 feet for bottom unloading.
Minimum Clearance Distances Measured Horizontally Between the Track Side of a Loading or Unloading Rack or Terminal and the Gauge Side of the Nearest Rail of Any Track
Minimum Distance from gauge side of nearest rail | |
---|---|
STRAIGHT TRACK | |
| 6 feet |
| 3 feet 7¾ inchesFootnote for TABLE II Minimum Clearance Distances Measured Horizontally Between the Track Side of a Loading or Unloading Rack or Terminal and the Gauge Side of the Nearest Rail of Any Track* |
| 6 feet |
CURVED TRACK | |
All distances prescribed for straight track shall be increased by 1 inch per degree of track curvature. |
Return to footnote *Except in Newfoundland where the distance shall be 3 feet 10 inches.
Minimum Distances of Storage Tanks from Main Tracks, Other Tracks, Property Lines and Buildings
Classification | Nominal Capacity Imperial Gallons | Minimum Distance (Feet) to Nearest Point of Above Ground Storage Tank Shell from | ||||
---|---|---|---|---|---|---|
Flammable Liquids | Single Storage Tank | Main Track | Any Track Other than Main Track | Property line of any adjacent Property that has been or may be built upon | Grain Elevators, Warehouses containing combustible Materials or other Dangerous Commodities; Engine Houses, Railway Shops and Other Similar off-site Buildings | Stations, Office Buildings and Other Similar Places of Public Assembly, and nearest residence |
(Gauge side of nearest rail) | ||||||
Class I 80°F and below | 0 — 5,000 | 30 | 20 | 10 | 20 | 40 |
5,001 — 15,000 | 50 | 20 | 15 | 75 | 150 | |
15,001 — 25,000 | 70 | 20 | 20 | 100 | 200 | |
25,001 — 50,000 | 90 | 20 | 30 | 125 | 250 | |
50,001 — 100,000 | 120 | 20 | 50 | 150 | 300 | |
100,001 — 200,000 | 150 | 20 | 70 | 175 | 350 | |
Over 200,000 | 200 | 20 | 100 | 200 | 400 | |
Class II Above 80°F Below 175°F | One-half the Distance Prescribed for Class I Flammable Liquids, but in no case shall the distance from any track or building be less than 20 feet, and the distance from the property line be less than 10 feet. | |||||
Class III | One and one-half times Distance Prescribed for Class I Flammable Liquid |
Classification | Nominal Capacity Imperial Gallons | Minimum Distance (Feet) to Nearest Point of Below Ground storage Tank Shell |
---|---|---|
Class I Class II} Class III | One-half distance prescribed for like class of flammable liquids and like storage capacities, but in no case shall the distance from any track be less than 20 feet. |