Energy Efficiency Regulations, 2016

Version of section 186 from 2017-06-28 to 2019-12-11:


Marginal note:Definitions

 The following definitions apply in this Division.

CSA C656-05

CSA C656-05 means the CSA standard CAN/CSA-C656-05 entitled Performance Standard for Split-System and Single-Package Central Air Conditioners and Heat Pumps. (CSA C656-05)

CSA C656-14

CSA C656-14 means the CSA standard CAN/CSA-C656-14 entitled Performance Standard for Split-System and Single-Package Central Air Conditioners and Heat Pumps. (CSA C656-14)

CSA C746-06

CSA C746-06 means the CSA standard CAN/CSA-C746-06 entitled Performance Standard for Rating Large and Single Packaged Vertical Air Conditioners and Heat Pumps. (CSA C746-06)

CSA C13256-1

CSA C13256-1 means the CSA standard CAN/CSA-C13256-1-01 entitled Water-Source Heat Pumps — Testing and Rating for Performance — Part 1: Water-to-Air and Brine-to-Air Heat Pumps. (CSA C13256-1)

small-duct and high-velocity

small-duct and high-velocity means, with respect to a split-system heat pump or a single package heat pump, one that has an indoor blower and coil combination that

  • (a) produces at least 300 Pa (1.2 inches of water) external static pressure when operated at an air volume rate of 104 to 165 L/s (220 to 350 cubic feet/minute) per nominal ton of cooling; and

  • (b) uses room outlets that produce velocities greater than 5 m/s (1,000 feet/minute) and that each have an area less than 39 cm2 (6 square inches). (à grand débit et à petits conduits)