Marginal note:Three test runs

  •  (1) A stack test consists of three consecutive test runs conducted within a period of 48 hours, each of which lasts at least 30 minutes and results in a determination of the boiler’s or heater’s NOx emission intensity.

  • Marginal note:Operating conditions for test runs

    (2) The test runs must be conducted while the boiler or heater meets the following conditions:

    • (a) it is operating with at least 50% of the input energy in its combustion chamber resulting from the introduction of gaseous fossil fuel;

    • (b) it is operating at at least 60% of its rated capacity;

    • (c) it is operating at a steady state;

    • (d) it is operating with preheated air, if it is equipped to preheat air; and

    • (e) the same type of gaseous fossil fuel — natural gas or alternative gas — is introduced into its combustion chamber.