SCHEDULE II
(s. 6.5)
LEVELS OF LIGHTING IN INDUSTRIAL AREAS
| Column I | Column II | |
|---|---|---|
| Item | Area | Level in lx |
| 1. | GARAGES | |
(a) Main repair and maintenance areas, other than those referred to in paragraph (b) ![]() | 300 | |
(b) Main repair and maintenance areas used for repairing and maintaining cranes, bulldozers and other major equipment ![]() | 150 | |
(c) General work areas adjacent to a main repair and maintenance area referred to in paragraph (b) ![]() | 50 | |
(d) Fuelling areas ![]() | 150 | |
(e) Battery rooms ![]() | 100 | |
| (f) Other areas in which there is | ||
| 100 | |
| 50 | |
| 2. | LABORATORIES | |
(a) Areas in which instruments are read and where errors in such reading may be hazardous to the health or safety of an employee ![]() | 750 | |
(b) Areas in which a hazardous substance is handled ![]() | 500 | |
(c) Areas in which laboratory work requiring close and prolonged attention is performed ![]() | 500 | |
(d) Areas in which other laboratory work is performed ![]() | 300 | |
| 3. | LOADING PLATFORMS, STORAGE ROOMS AND WAREHOUSES | |
(a) Areas in which packages are frequently checked or sorted ![]() | 250 | |
(b) Areas in which packages are infrequently checked or sorted ![]() | 75 | |
(c) Docks (indoor and outdoor), piers and other locations where packages or containers are loaded or unloaded ![]() | 150 | |
(d) Areas in which grain or granular material is loaded or unloaded in bulk ![]() | 30 | |
(e) Areas in which goods are stored in bulk or where goods in storage are all of one kind ![]() | 30 | |
(f) Areas where goods in storage are of different kinds ![]() | 75 | |
(g) Any other area ![]() | 10 | |
| 4. | MACHINE AND WOODWORKING SHOPS | |
(a) Areas in which medium or fine bench or machine work is performed ![]() | 500 | |
(b) Areas in which rough bench or machine work is performed ![]() | 300 | |
(c) Any other area ![]() | 200 | |
| 5. | MANUFACTURING AND PROCESSING AREAS | |
(a) Major control rooms or rooms with dial displays ![]() | 500 | |
| (b) Areas in which a hazardous substance is processed, manufactured or used | ||
| 500 | |
| 200 | |
| (c) Areas in which substances that are not hazardous substances are processed, manufactured or used or where automatically controlled equipment operates | ||
| 100 | |
| 50 | |
| 6. | SERVICE AREAS | |
| (a) Stairways and elevating devices that are | ||
| 100 | |
| 50 | |
(b) Stairways that are used only in emergencies ![]() | 30 | |
| (c) Corridors and aisles that are used by persons and mobile equipment | ||
| 100 | |
| 50 | |
(d) Corridors and aisles that are used by mobile equipment only ![]() | 50 | |
| (e) Corridors and aisles that are used by persons only and are | ||
| 50 | |
| 30 |
- SOR/88-68, s. 14;
- SOR/89-515, s. 1;
- SOR/94-263, s. 13;
- SOR/96-525, s. 11;
- SOR/2002-208, ss. 40, 43(F).